Measuring principle Measured current Rated current Precision Recommended interval between calibrations Digital output
Fiber optical based on Faraday effect, not affectable to external magnetic fields DC, AC, DC+AC From 10 up to 14 000kA ±0.1%, ±0.2%, ±0.5%, ±1.0% 6 years for ±0.2%, ±0.5%, ±1.0% accuracy 3 years for 0.1% accuracy Modbus RTU IEA485
Logical outputs Sampling rate Dimensions
Open collector, configurable polarity and switching logic Up to 14400 1/sec, configurable Electronic unit (WxHxD, mm) 482x132x350, Front panel maintenance
Analog outputs
0..20mA/4..20mA/±0..20mA, configurable source, mode and rated current 0..1V/±0..1V, configurable source, mode and rated current
Electronic unit
Sensing element
Environment conditions Power supply IP rating
IEC 61850-3. T = 0 °C to +45 °C 24 20% VDC, 1A IP20
IEC 61850-3. T = -40 °C to +70 °C N/A. Passive fiber sensor IP67
Sensing element
Temperature sensor
HMI panel display
ORDERING INFORMATION
Specification code
GMS-FCS-DC-AA-BB1CC1-BB2CC2-DD-EE-FF
GMS FSC DC
Green-metering solutions Fiber-optical current sensor For DC applications (no digital IEC 61850-9-2 sampling output)
AA
Quantity of measuring channels 1 One measuring channel 2 Two measuring channels
BB1
Precision in range of 10..100% of selectable rated current for first channel 01 ±1% 02 ±2% 05 ±5% 10 ±0%
CC1
Optical sensor limits for rated current range for first channel. Option CR1-CR4 should be specified, combination of options available. SR Standard range from 10 up to 350kA ER Extended range from 100 up to 700kA UR Ultra-high range from 800 up to 14000kA
DD
Type of analog and logical outputs (Digital ModbusRTU output always installed) 01 1 х (0..20mA/4..20mA/±0..20mA) 1 х (0..1V/±0..1V) 3 x logical 02 2 х (0..20mA/4..20mA/±0..20mA) 2 х (0..1V/±0..1V) 6 x logical
EE
Temperature range for sensors 01 25 °C to +55 °C 02 0 °C to +45 °C 03 –10 °C to +50 °C 04 –20 °C to +60 °C 05 –30 °C to +65 °C 06 –40 °C to +70 °C IR Individual range, declared in specification
FF
Distance between Electronic unit and sensor in meters
Options
HMI PS220DC PS230AC CR1 CR2 CR3 CR4
HMI display for panel mounting DIN-rail power supply for electronic unit from 220VDC power source DIN-rail power supply for electronic unit from 230VAC power source Current range for sensor: from 0 to 25% of basic optical sensor limits range Current range for sensor: from 25 to 50% of basic optical sensor limits range Current range for sensor: from 50 to 75% of basic optical sensor limits range Current range for sensor: from 75 to 100% of basic optical sensor limits range